Inspection History Details
Inspection Status: Compliance
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
Case Number - T07FR00056
Inspection Description - VIOL - BUILDING SVCS & SYSTEMS
Inspection Status - Compliance
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/12/2007 | VIOL - BUILDING SVCS & SYSTEMS | Compliance | All violations have been corrected. | |
01/09/2007 | VIOL - BUILDING SVCS & SYSTEMS | Violation | 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. Cap ends of open wire splice ( in basement Main Supply Room) and place in a junction box. | |
01/09/2007 | VIOL - BUILDING SVCS & SYSTEMS | Violation | 605.3 Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space. Remove stored materials near electrical panel in the Sprinkler Riser Room. |