Case: T07FR00056

Parcel: 128100560


Addresses:

310 S WILLIAMS BL


Inspection Status: Compliance

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T07FR00056

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Compliance

Date Description Inspector Results Comments
06/12/2007 VIOL - BUILDING SVCS & SYSTEMS Compliance All violations have been corrected.
01/09/2007 VIOL - BUILDING SVCS & SYSTEMS Violation 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. Cap ends of open wire splice ( in basement Main Supply Room) and place in a junction box.
01/09/2007 VIOL - BUILDING SVCS & SYSTEMS Violation 605.3 Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space. Remove stored materials near electrical panel in the Sprinkler Riser Room.