Inspection History Details
Inspection Status: Compliance
Inspection History: VIOL - FIRE SERVICE FEATURES
Case Number - T07FR00056
Inspection Description - VIOL - FIRE SERVICE FEATURES
Inspection Status - Compliance
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/12/2007 | VIOL - FIRE SERVICE FEATURES | Compliance | All violations have been corrected. | |
01/09/2007 | VIOL - FIRE SERVICE FEATURES | Violation | 508.5.4 Obstruction. Posts, fences, vehicles, growth, trash, storage and other materials or objects shall not be placed or kept near fire hydrants, fire department inlet connections or fire protection system control valves in a manner that would prevent such equipment or fire hydrants from being immediately discernible. The fire department shall not be deterred or hindered from gaining immediate access to fire protection equipment or fire hydrants. Cut hedge at least 3 feet away from the Fire Department Connections located on the East Building Wall. | |
01/09/2007 | VIOL - FIRE SERVICE FEATURES | Violation | 506.1 Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. Provide keys to access main entrance gates, sprinkler riser room, fire alarm control panel room. | |
01/09/2007 | VIOL - FIRE SERVICE FEATURES | Violation | 510.1 Identification. Fire protection equipment shall be identified in an approved manner. Rooms containing controls for airconditioning systems, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible. Install identification signs on upstairs AC/ Boiler room, Sprinkler Riser Room, and basement Fire Alarm Control Panel Room. |