Inspection Status: Approved
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/22/2007 | VIOL - FIRE PROTECTION SYSTEMS | Approved | ||
| 01/12/2007 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | TFC 315.2.1 - Ceiling clearance. Storage shall be maintained ... a minimum of 18 inches below sprinkler head deflectors in sprinklered areas of buildings. _____ Remove storage and display to 18 inches or more below sprinkler head. |