Case: T07FR00054

Parcel: 13409018C


Addresses:

8628 E BROADWAY BL


Inspection Status: Approved

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T07FR00054

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
03/22/2007 VIOL - BUILDING SVCS & SYSTEMS Approved
01/12/2007 VIOL - BUILDING SVCS & SYSTEMS Correction Required TFC 605.5 - Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact.

_____ Extension cord shall not extend under any rug or carpet. Protect from impact with approved protective runner

TFC 605.9 - Temporary wiring for electrical power and lighting installations is allowed for a period not to exceed 90 days. Temporary wiring methods shall meet the applicable provisions of the ICC Electrical Code.

_____ Repair/replace fluorescent fixtures and remove temporary lighting fixtures and wiring.