Case: T07FR00053

Parcel: 13803031Q


Addresses:

902 W VALENCIA RD

Inspection Status: Approved

Inspection History: VIOL - MEANS OF EGRESS

Date Description Inspector Results Comments
01/23/2007 VIOL - MEANS OF EGRESS Approved 1.---All Signs repaired.
01/23/2007 VIOL - MEANS OF EGRESS Approved 2.---All lighting repaired.
01/08/2007 VIOL - MEANS OF EGRESS Violation 1. EXIT SIGNS OUT
-Main entrance
-Rear center exit
***Repair signs
1026.3 Exit sign illumination. Exit signs shall be internally or
externally illuminated. The face of an exit sign illuminated from
an external source, shall have an intensity of not less than 5
foot-candles (54 lux). Internally illuminated signs shall provide
equivalent luminance and be listed for the purpose.IFC2003
01/08/2007 VIOL - MEANS OF EGRESS Violation 2. EMERGENCY LIGHTING OUT
-Main entrance
-Rear center exit
***Repair to working condition
1006.3 Illumination emergency power. The power supply for
means of egress illumination shall normally be provided by the
premise's electrical supply.
In the event of power supply failure, an emergency electrical
system shall automatically illuminate area.IFC2003