Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - FIRE RESIST.RATED CONST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/23/2007 | VIOL - FIRE RESIST.RATED CONST | Approved | 3.---All tiles replaced/reseated. | |
| 01/23/2007 | VIOL - FIRE RESIST.RATED CONST | Approved | 4.---All wires/cords through ceiling removed. All wiring in approved conduit. | |
| 01/08/2007 | VIOL - FIRE RESIST.RATED CONST | Violation | 3.MISSING CEILING TILES -NW shelf storage room (3) -NW rear exit (3) -SE corner, Juniors section (1) -Stockroom, over doorway, over East wall (2) -Reseat tile over Toy section (1) ***Replace missing tiles and reseat any loose tiles. 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire.IFC2003 |
|
| 01/08/2007 | VIOL - FIRE RESIST.RATED CONST | Violation | 4. WIRES/CORDS THROUGH CEILING -Rear exit area -Rear office ***Remove cords protruding through ceiling. Use approved methods to route wiring and preserve fire-resistive construction. 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire.IFC2003 |