Case: T07FR00032

Parcel: 11623142D


Addresses:

1010 S FREEWAY


Inspection Status: Approved

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T07FR00032

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Approved

Date Description Inspector Results Comments
12/17/2007 VIOL - MEANS OF EGRESS Approved
01/23/2007 VIOL - MEANS OF EGRESS Partial Approval All abated.
01/04/2007 VIOL - MEANS OF EGRESS Correction Required Wire prohibiting operation of Ballroom panic hardware:
TFC 1027.6 [ammendment] Panic Hardware:
Where panic hardware and fire exit hardware is installed, whether required or not, panic or fire exit hardware shall be the only locking device on the door except where otherwise permitted in this code.

_OK___Remove wire, and keep clear of any constraint in the future.
01/04/2007 VIOL - MEANS OF EGRESS Correction Required Exit signs not lit:
TFC 1026.3 Exit sign illumination. Exit signs shall be internally or externally illuminated.

OK_____Fix light in exit signs.
[Bar, Ballroom]
01/04/2007 VIOL - MEANS OF EGRESS Correction Required Emergency lighting:
TFC 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the area.

OK____Fix the existing emergency lighting. [Office- note: office is currently being painted. It shall be restored in a safe manner as soon as practicable, including switch covers, emergency lighting, fused power cords, etc.]