Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
Case Number - T07FR00032
Inspection Description - VIOL - BUILDING SVCS & SYSTEMS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/17/2007 | VIOL - BUILDING SVCS & SYSTEMS | Approved | ||
01/23/2007 | VIOL - BUILDING SVCS & SYSTEMS | Partial Approval | Still have holes in electrical panels; Blocked electrical panels; Remove multiplug adapter in Bar please, and replace with fused power strip. | |
01/04/2007 | VIOL - BUILDING SVCS & SYSTEMS | Correction Required | Extension cords: TFC 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____Replace with approved power strip. [Bar, office, by kitchen door.] |
|
01/04/2007 | VIOL - BUILDING SVCS & SYSTEMS | Correction Required | Open space in electrical panel and Switch covers and other misc: TFC 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. Please correct the following items: _____Place an approved "blank" in the space. [Kitchen] _____Repair kitchen bathroom appliance [on ceiling]. _____Ballroom AC closet [open wiring]. _____Kitchen and Bar [switch cover plate]. _____Closet off Dining room- [Secure wiring, stop leak, and either service appliance in an approved manner, or disconnect in an approved manner, and mark it as such] _____Remove or repair all yard flood light hardware, wiring and bulbs. |
|
01/04/2007 | VIOL - BUILDING SVCS & SYSTEMS | Correction Required | Blocked electrical panel: TFC 605.3 Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. _____Clear area in front of electrical panel in an approved manner. [Ballroom electrical, and "Electrical Room"] |