Permit: T07EL02240

Parcel: 117080540


Addresses:

802 S 4TH AV


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07EL02240

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/18/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
01/17/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
GAS TO ALL UNITS MUST BE BONDED
YOU ONLY BONDED "B" GAS PIPE?
01/03/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. GAS PIPE BONDING IS TO BE ON CUSTOMER SIDE OF GAS METER, ALL FOUR UNITS, ALSO, WHERE DID YOU BOND THE WATER PIPING?
2. A COMMON J-BOX WAS USED FOR ALL UNITS, PLEASE TAG CONDUCTORS IN J-BOX AT SERVICE AS TO SERVICE BREAKER USED, OR UNIT #