Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07EL02240
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/18/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
01/17/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* GAS TO ALL UNITS MUST BE BONDED YOU ONLY BONDED "B" GAS PIPE? |
|
01/03/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. GAS PIPE BONDING IS TO BE ON CUSTOMER SIDE OF GAS METER, ALL FOUR UNITS, ALSO, WHERE DID YOU BOND THE WATER PIPING? 2. A COMMON J-BOX WAS USED FOR ALL UNITS, PLEASE TAG CONDUCTORS IN J-BOX AT SERVICE AS TO SERVICE BREAKER USED, OR UNIT # |