Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/22/2009 | ELECTRIC - FINAL | Approved | ||
| 04/21/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* PLANS NOT ACCURATE, REVISED PLANS TO REFLECT SITE CONDITIONS, ONE LINE, FUTURE 200A DISC. PANEL L1? PLANS NEED TO BE APPROVED THRU PLAN CK. C.O.T. |
|
| 04/09/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. CALL FOR FINAL AFTER POWER CHECK AND REMOVAL OF TEMP ELECTRICAL 2. CLEARANCE FOR NEW SERVICE WILL BE SENT TODAY 3. PROVIDE REVISED PLANS, ELECTRICAL SYSTEM 4. FILL IN UNUSED OPENINGS ON DEAD FRONTS OF PANELS |
|
| 04/08/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) SERVICE GROUND MODIFICATIONS NOT COMPLETE YET-OK 2) INSIDE SEALING FOR DUST IN DEVICES OK 3) REVISED PLAN NOT ON SITE 4) INSTALL ADDRESS LABEL ON SERVICE |
|
| 04/06/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. COMPLETE INTERIOR MODIFICATIONS FOR COMPLIANCE WITH NEC AND COT AMENDMENTS FOR WOOD WORKING FACILITY -- PLANS TO BE ON SITE. |
|
| 02/19/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. BONDING JUMPERS ON SUPPLY SIDE OF SERVICE TO COMPLY WITH 250 102 C 2. REVISE PLAN TO REFLECT INSTALLATION 3. WIRING METHODS MUST BE PER C.O.T CODE AMENDMENTS TO NEC 4. COPY OF COT AMENDMENTS LEFT WITH CONTR. 5. WATER PIPE BOND PER 250-104 6. ID HIGH LEG PER NEC 230.56, 408.3 7. THIS IS A WOODWORKING CABINET SHOP NOT CLASSIFIED PER PLAN. WIRING METHODS TO COMPLY WITH 500 ARTICLES NEC ALSO EXISTING WIRING |
|
| 02/18/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 02/17/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CANCELED BY OFFICE BEFORE CANCELLATION BORRIS GEFTNER ON INSPECTOR SANTA CRUZ'S SPEAKERPHONE IN THE ELECTRICAL SECTION OFFICE THREATENED BODILY HARM TO INSPECTOR HOLLANDER. HE STATED IF RICK SHOWED UP ON HIS JOB HE WOULD KICK HIS A** |