Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07EL02216
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/18/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
01/02/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE A LISTED MAST BRACE - NEC 230.28 2. PROVIDE A ROOF FLASHING FOR SERVICE MAST 3. NEED TO USE HUB FOR METER BASE AS LISTED INSIDE METER BASE LABEL - NEC 110.3B - THIS LABEL SAYS METER BASE IS UNDERGROUND FEED ONLY 4. NEED PROPER FRONT CLEARANCE FOR METER BASE - NEC 110.26 5. MAXIMUM HEIGHT FOR SERVICE DISCONNECT IS 6'7" - NEC 404.8 6. SEAL OPENINGS INTO PANEL - NEC 110.12, 312.5 7. RECONNECT TELCO GROUND 8. PROVIDE ACCESS TO ATTIC J-BOX 9. PANEL DIRECTORY TO BE CORRECT & LEGIBLE - NEC 408.4 10. IDENTIFY "SERVICE DISCONNECT" AS SUCH - NEC 230.72B PARTIAL INSPECTION |