Permit: T07EL02213

Parcel: 13205015V


Addresses:

3450 E 36TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/18/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
01/22/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. RECEIVED LETTER OF TORQUE FOR SES
2. PROVIDE OR INSTALL BUSHING AT CONDUIT ENDS
AT BOTTOM OF SERVICE AND MCC EQUIP. AS REQUIRED
BY 300-5-H NEC
3. BRACE FEEDERS AS REQUIRED BY MANUF.
4. NEED APPROVAL FROM ENGINEER OF RECORD FOR SERVICE EQUIP. AND MCC FIELD INSTALLATION. MAIN LOADS (400a) NOT SPLIT AS SHOWN ON PLANS
5. RECALL INSPECTION FOR FIELD CHECK OUT OF FEEDERS AND MOTOR DISCONNECTING
01/20/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. RECALL INSP. LEAVE PH.# OF CONTRACTOR ON SITE AND REMOVE COVERS TO ELECTRICAL EQUIP. FOR INSPECTION
2. PROVIDE LETTER OF TORQUE FOR SERVICE EQUIP.
3. POST BOND AT 201 N. STONE FOR TEMP POWER FOR TEST THIS MUST BE DONE IN ORDER TO ENERGIZE NEW SERVICE