Permit: T07EL02199

Parcel: 10818716A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/09/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/03/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
03/13/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. WIRING NOT DONE PER PLAN. EITHER WIRE PER PLAN OR REVISE PLAN AND RESUBMIT FOR REVIEW
2. MC TO BE PROPERLY SECURED/SUPPORTED THROUGH CEILING 6' INTERVALS - NOT LAYING ON OR SUPPORTED BY OTHER EQUIPMENT - NEC 330.30
3. MINIMUM SIZE GROUND TO BOXES FOR 30 AMP CKT
IS #10 CU - NEC 250.122

OK WALL COVER
01/29/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. WALLS COVERED WITHOUT INSPECTIONS
2. HAVE ELECTRICIAN PRESENT TO OPEN PANEL
3. BOXES MORE THAN 1/4" FROM BOX TO SURFACE 314.20
4. PLEASE VERIFY LISTING OF OVEN
5. ELECTRIC WIRING NOT AS PER PLANS
6. MAINTAIN WORKING CLEARANCES PER 110.26