Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07EL02199
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/09/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
04/03/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
03/13/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. WIRING NOT DONE PER PLAN. EITHER WIRE PER PLAN OR REVISE PLAN AND RESUBMIT FOR REVIEW 2. MC TO BE PROPERLY SECURED/SUPPORTED THROUGH CEILING 6' INTERVALS - NOT LAYING ON OR SUPPORTED BY OTHER EQUIPMENT - NEC 330.30 3. MINIMUM SIZE GROUND TO BOXES FOR 30 AMP CKT IS #10 CU - NEC 250.122 OK WALL COVER |
|
01/29/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. WALLS COVERED WITHOUT INSPECTIONS 2. HAVE ELECTRICIAN PRESENT TO OPEN PANEL 3. BOXES MORE THAN 1/4" FROM BOX TO SURFACE 314.20 4. PLEASE VERIFY LISTING OF OVEN 5. ELECTRIC WIRING NOT AS PER PLANS 6. MAINTAIN WORKING CLEARANCES PER 110.26 |