Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
Permit Number - T07EL02194
Inspection Description - ELECTRIC - RECONNECT
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/16/2008 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
| 01/07/2008 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL MISSING PLATES ON SWITCHES & RECEPTACLES 2. KITCHEN COUNTER RECEPTACLES TO BE GFI PROTECTED 3. SMOKE DETECTORS NOT INSTALLED PROPERLY TO BE 3' FROM VENTS & WITHIN 4"-12" OF CEILING IF MOUNTED ON WALLS 4. BATHROOM LIGHT NOT WIRED PROPERLY NEEDS JUNCTION BOX AND MISSING COVER 5. WIRES HANGING OUT OF WALL ABOVE RANGE. MISSING EXHAUST HOOD |