Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/16/2008 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL GFI PROTECTED RECEPTS IN KITCHEN COUNTER AND BATHROOMS 2. SMOKE DETECTORS IN BEDROOMS MUST BE AT LEAST 3' AWAY FROM COOLER REGISTER 3. OBTAIN PERMITS & CALL FOR INSPECTIONS REQUIRED FOR ROOM ADDITION IN SOUTHEAST CORNER OF HOUSE 4. ALL COVERS IN EXISTING HOUSE FOR SWITCHES & RECEPTS MUST BE INSTALLED 5. PROVIDE LADDER FOR ROOF INSPECTION |