Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/20/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 12/19/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) GROUND RODS TO BE MINIMUM 6' APART 2) MULTI-WIRE BRANCH CKT'S TO TERMINATE ON SEPERATE PHASES 3) CHECK PANEL DIRECTORY 4) RE-GROUND TELCO |