Permit: T07EL02186

Parcel: 133224070


Addresses:

6852 E KINGSTON DR

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/18/2008 ELECTRIC - FINAL Approved
05/21/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. BOND JUNCTION BOX
2. FILL UNUSED PORTION OF OPENING IN BACK OF PANEL
WITH A NON-COMBUSTIBLE PRODUCT
3. ONLY ONE NEUTRAL CONDUCTOR TO A TERMINAL LUG
4. PLEASE VERIFY PERMIT FOR NEW WIRING TO INTERIOR
5. RECEPTACLE COVER TO BE WEATHERPROOF - 406.8
6. USE CORRECT SIZE BREAKER AMPACITY FOR NM/UF CABLES
7. PROTECT CONDUCTORS LARGER THAN #4
12/27/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) RECALL AFTER CROSSOVER
12/21/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) CONDUCTORS TO BE MARKED SUN LIGHT RESISTANT AND LISTED
2) USE AN APPROVED MAST BRACE KIT
3) GROUNDING ELECTRODE CONDUCTOR TO TERMINATE TO GROUNDED CONDUCTOR TERMINALS
4) ADDRESS LABEL TO BE PERMANENT METAL LABEL
5) PLEASE VERIFY GAS BOND