Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/09/2008 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 12/21/2007 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) BOND GAS PIPING ON HOUSE SIDE OF METER 2) BOTH ENDS OF PIPING USED FOR BRACING TO BE THREADED. CANNOT USE COMPRESSION CONNECTORS 3) OK GROUND RODS 4) OK WATER BOND 5) RECALL AFTER TEP TIE IN AND SWING OVER COMPLETE |
|
| 12/20/2007 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL LISTED MAST BRACING 2. INSTALL GROUND RODS MIN. 6' APART 3. BOND GAS PIPING 4. INSTALL SERVICE CONDUCTORS TO OVERHEAD POSITION IN METER SECTION 5. IDENTIFY NEUTRAL CONDUCTOR CLOSER TO WEATHERHEAD |
|
| 12/19/2007 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : Lock up dogs in the yard.| 910* 1. KNOCKED ON DOOR - NO ANSWER 2. PROVIDE ACCESS TO ELECTRIC SERVICE AND PLEASE HAVE DOGS LOCKED UP |