Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - UNDERGROUND
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/15/2008 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : The service is not per code.| 210* IN ADDITION TO PREVIOUS CORRECTIONS, THIS INSPECTOR CAN FIND NO REASON TO ENERGIZE THIS SERVICE AS THERE ARE NO LOADS CONNECTED TO IT POWER WILL NOT BE APPROVED WITHOUT A LEGITIMATE USE FOR SERVICE. IF LOADS ARE TO BE CONNECTED, THEY SHOULD BE IN PLACE AT TIME OF INSPECTION IN ADDITION TO PREVIOUS CORRECTIONS BEING PROPERLY COMPLETED |
|
| 02/12/2008 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : See detailed listing on site.| 999* PARTIAL INSPECTION 1. POINT OF ATTACHMENT NOT TO BE ABOVE WEATHERHEAD 2. SERVICE CONDUCTORS TO BE MINIMUM 10' ABOVE GRADE 3. BOND SERVICE ENCLOSURE 4. GROUNDING ELECTRODE CONDUCTOR - EMT TO BE MADE ELECTRICALLY CONTINUOUS 5. MULTIWIRE BRANCH CKTS TO TERMINATE ON SEPARATE PHASES 6. PROVIDE MAIN BREAKER AND HOLD DOWN KIT FOR PANEL 7. INSTALL ADDRESS TAG ON SERVICE 8. WORK TO BE DONE BY QUALIFIED ELECTRICIAN |