Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/30/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 01/14/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) NOTE: #201, 203 & 205 HAVE BEEN APPROVED-ONLY HAVE #117 & 217 LEFT |
|
| 01/10/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. REPAIRS TO G.E.C'S TO BE MADE PER CODE - IRREVERSIBLE CRIMP OR EXOTHERMIC WELD NOT SPLIT BOLT 2. NEED PROPER WEATHERPROOF COVERS FOR STAIRWELL J-BOXES |