Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/27/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 12/20/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. COPPER & ALUMINUM CONDUCTORS CANNOT BE SPLICED TOGETHER 2. NEUTRAL CONDUCTORS #6 & SMALLER TO BE IDENTIFIED ALONG ENTIRE LENGTH 3. INSTALL PROTECTIVE BUSHING ON 3/4" EMT WHERE 10/3 ROMEX ENTERS 4. SERVICE ENERGIZED PRIOR TO APPROVAL 5. COMPLETELY DRIVE GROUND RODS |