Permit: T07EL02160

Parcel: 136240760


Addresses:

6751 E NELSON DR

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/27/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
12/20/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. COPPER & ALUMINUM CONDUCTORS CANNOT BE SPLICED TOGETHER
2. NEUTRAL CONDUCTORS #6 & SMALLER TO BE IDENTIFIED ALONG ENTIRE LENGTH
3. INSTALL PROTECTIVE BUSHING ON 3/4" EMT WHERE 10/3 ROMEX ENTERS
4. SERVICE ENERGIZED PRIOR TO APPROVAL
5. COMPLETELY DRIVE GROUND RODS