Permit: T07EL02150

Parcel: 128062040


Addresses:

6052 E BEVERLY ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
12/17/2007 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
12/14/2007 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
1) CANNOT USE PLASTIC BOX WITH METAL RACEWAY
2) NEUTRAL CONDUCTORS #6 AND SMALLER TO BE IDENTIFIED ENTIRE LENGTH
3) SEAL OPENING IN BACK OF PANEL WITH NON-COMBUSTIBLE MATERAIL
4) OK GROUND RODS
5) OK WATER AND GAS BOND