Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/17/2007 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 12/14/2007 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) CANNOT USE PLASTIC BOX WITH METAL RACEWAY 2) NEUTRAL CONDUCTORS #6 AND SMALLER TO BE IDENTIFIED ENTIRE LENGTH 3) SEAL OPENING IN BACK OF PANEL WITH NON-COMBUSTIBLE MATERAIL 4) OK GROUND RODS 5) OK WATER AND GAS BOND |