Permit: T07EL02145

Parcel: 130083610


Addresses:

3520 E SYLVANE ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
03/07/2008 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
12/14/2007 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. STRAP #4 BARE GROUND TO WALL OF HOUSE
2. NEED TO VERIFY WATER PIPE BONDING
3. INSULATING BUSHING REQUIRED ON 1 1/2" CONNECTORS AT TOP OF PANEL
4. INSTALL PERMANENT ADDRESS LABEL ON SERVICE
5. USE 1/4" MIN. BOLTS TO SUPPORT RISER STRAP, DRYWALL SCREWS NOT STRONG ENOUGH.