Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/07/2008 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 12/14/2007 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. STRAP #4 BARE GROUND TO WALL OF HOUSE 2. NEED TO VERIFY WATER PIPE BONDING 3. INSULATING BUSHING REQUIRED ON 1 1/2" CONNECTORS AT TOP OF PANEL 4. INSTALL PERMANENT ADDRESS LABEL ON SERVICE 5. USE 1/4" MIN. BOLTS TO SUPPORT RISER STRAP, DRYWALL SCREWS NOT STRONG ENOUGH. |