Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/11/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* FINISH #5 OF PREVIOUS INSPECTION |
|
| 12/28/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. USE APPROVED SEALING DEVICES AT TOP OF PANEL 2. WHERE IS GROUNDED CONDUCTOR FOR SUB-PANEL CONNECTED? OLD SYSTEM IS AN UNGROUNDED SYSTEM NEED TO SEE CONNECTIONS 3. BREAKERS TO BE LISTED FOR USE BY MANUFACTURE 4. DISCONNECTING MEANS NEEDED FOR WATER HEATER 5. PLEASE VERIFY PERMIT FOR NEW WATER HEATER |
|
| 12/18/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) RECALL FOR LOAD CONNECTION ON 12/19/07 2) USE APPROVED STRAPS FOR GROUNDS |