Permit: T07EL02131

Parcel: 107130690


Addresses:

8 W KELSO ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/14/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
12/10/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. INSTALL LOCKNUT & BOND BUSHING ON NIPPLE IN METER SOCKET
2. MAIN BREAKER TO HAVE MANUFACTURE HOLD DOWN
3. CORD NOT ALLOWED FOR PERMANENT WIRING METHOD
4. PLEASE VERIFY ELECTRICAL PVC CONDUIT & ELBOWS & FITTINGS
5. LABEL BREAKERS AS PER 408.4
6. USE LISTED MAST BRACE KIT - BRACE TO BE EFFECTIVE
7. UNIT TO BE OPEN FOR RECONNECT