Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/14/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 12/10/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. INSTALL LOCKNUT & BOND BUSHING ON NIPPLE IN METER SOCKET 2. MAIN BREAKER TO HAVE MANUFACTURE HOLD DOWN 3. CORD NOT ALLOWED FOR PERMANENT WIRING METHOD 4. PLEASE VERIFY ELECTRICAL PVC CONDUIT & ELBOWS & FITTINGS 5. LABEL BREAKERS AS PER 408.4 6. USE LISTED MAST BRACE KIT - BRACE TO BE EFFECTIVE 7. UNIT TO BE OPEN FOR RECONNECT |