Permit: T07EL02116

Parcel: 11812060A


Addresses:

215 E 23RD ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/28/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
12/10/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. GROUND ELECTRICAL SERVICE PER CODE - 2 GROUND
RODS 6' MIN. APART - IT APPEARS THAT THE WATER PIPE GOING INTO THE HOUSE IS THE ONLY THING GROUNDING THE SERVICE, ALSO, INSTALL BLANK FOR MISSING BREAKER IN PANEL
2. INSTALL GFI PROTECTED OUTLETS FOR KITCHEN & BATHROOM
3. REPAIR RECEPT. BOXES FALLING OUT OF WALLS AND COVER ALL SWITCHES & RECEPTS
4. SMOKE DETECTORS REQUIRED IN BEDROOMS AND HALLWAY
5. CAP OFF WIRING & COVER BOX IN PORCH