Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/28/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 12/10/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. GROUND ELECTRICAL SERVICE PER CODE - 2 GROUND RODS 6' MIN. APART - IT APPEARS THAT THE WATER PIPE GOING INTO THE HOUSE IS THE ONLY THING GROUNDING THE SERVICE, ALSO, INSTALL BLANK FOR MISSING BREAKER IN PANEL 2. INSTALL GFI PROTECTED OUTLETS FOR KITCHEN & BATHROOM 3. REPAIR RECEPT. BOXES FALLING OUT OF WALLS AND COVER ALL SWITCHES & RECEPTS 4. SMOKE DETECTORS REQUIRED IN BEDROOMS AND HALLWAY 5. CAP OFF WIRING & COVER BOX IN PORCH |