Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/28/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 01/14/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. MAST APPEARS TO BE BENDING TOWARD SERVICE DROP CONDUCTORS. NEEDS ADDITIONAL BRACING 2. COMPLETE ITEM #2 FROM INSPECTION ON 12/18/07 |
|
| 12/18/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) GROUNDING ELECTRODE CONDUCTOR TO TERMINATE ON NEUTRAL BAR-NEEDS TO BE CONTINOUS 2) MARK "SERVICE DISCONNECT" 3) PARTIAL APPROVAL BASED ON REMOVAL OF GUTTER IN 10 BUSINESS DAYS. MUST RECALL FOR INSPECTION AT THIS TIME FRAME OR TEP WILL BE CALLED TO DISCONNECT SERVICE |
|
| 12/11/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* NO INSPECTION AT THIS TIME DUE TO RAIN COMPLETE ALL PREVIOUS CORRECTIONS ALSO, SERVICE MAST NOT TO PENETRATE RAIN GUTTER TAKE CARE OF ALL ITEMS WRITTEN BEFORE CALLING BACK FOR FINAL |
|
| 12/07/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. TURN WEATHERHEAD TO POINT OUT INSTEAD OF OVER ROOFTOP 2. IDENTIFY SERVICE NEUTRAL AS IT LEAVES THE WEATHERHEAD 3. BRACE FOR MAST MUST SECURE INTO SOLID STRUCTURE - NOT JUST ROOF SHEATHING 4. PROVIDE PROPER SEALING/FLASHING FOR MAST THROUGH GUTTER 5. NEED INHIBITOR ON AL ALUMINUM TERMINATIONS 6. LOCKNUT IN METER BASE IS ON BACKWARDS 7. ARRANGE BONDING CONDUCTORS TO PREVENT OBJECTIONABLE CURRENT 8. IDENTIFY "SERVICE DISCONNECT" AS SUCH 9. HANDLE FOR SERVICE DISCONNECT TO BE MAXIMUM 6'7" FROM GRADE IN ON POSITION 10. PROVIDE NEW GROUND RODS AND WATER/GAS BONDING FOR SERVICE. |