Permit: T07EL02108

Parcel: 11108177J


Addresses:

3731 E GRANT RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/28/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
01/14/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. MAST APPEARS TO BE BENDING TOWARD SERVICE DROP CONDUCTORS. NEEDS ADDITIONAL BRACING
2. COMPLETE ITEM #2 FROM INSPECTION ON 12/18/07
12/18/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) GROUNDING ELECTRODE CONDUCTOR TO TERMINATE ON NEUTRAL BAR-NEEDS TO BE CONTINOUS
2) MARK "SERVICE DISCONNECT"
3) PARTIAL APPROVAL BASED ON REMOVAL OF GUTTER IN 10 BUSINESS DAYS. MUST RECALL FOR INSPECTION AT THIS TIME FRAME OR TEP WILL BE CALLED TO DISCONNECT SERVICE
12/11/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
NO INSPECTION AT THIS TIME DUE TO RAIN
COMPLETE ALL PREVIOUS CORRECTIONS
ALSO, SERVICE MAST NOT TO PENETRATE RAIN GUTTER
TAKE CARE OF ALL ITEMS WRITTEN BEFORE CALLING BACK FOR FINAL
12/07/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. TURN WEATHERHEAD TO POINT OUT INSTEAD OF OVER ROOFTOP
2. IDENTIFY SERVICE NEUTRAL AS IT LEAVES THE WEATHERHEAD
3. BRACE FOR MAST MUST SECURE INTO SOLID STRUCTURE - NOT JUST ROOF SHEATHING
4. PROVIDE PROPER SEALING/FLASHING FOR MAST THROUGH GUTTER
5. NEED INHIBITOR ON AL ALUMINUM TERMINATIONS
6. LOCKNUT IN METER BASE IS ON BACKWARDS
7. ARRANGE BONDING CONDUCTORS TO PREVENT OBJECTIONABLE CURRENT
8. IDENTIFY "SERVICE DISCONNECT" AS SUCH
9. HANDLE FOR SERVICE DISCONNECT TO BE MAXIMUM 6'7" FROM GRADE IN ON POSITION
10. PROVIDE NEW GROUND RODS AND WATER/GAS BONDING FOR SERVICE.