Permit: T07EL02105

Parcel: 131040710


Addresses:

4809 E 24TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
12/11/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
12/05/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL LISTED MAST BRACING
2. CANNOT ENTER PANEL WITH LOAD CONDUCTORS THROUGH METER SECTION
3. INSTALL BREAKERS LISTED FOR USE IN PANEL
4. NEUTRAL CONDUCTORS & GROUNDING CONDUCTORS #6 AND SMALLER TO BE IDENTIFIED ALONG ENTIRE LENGTH.
5. THIS IS NOT A PANEL REPAIR THE SERVICE WAS RELOCATED & NEW PANEL WAS INSTALLED DESCRIPTION NEEDS TO BE REVISED
6. OK GROUND RODS & WATER/GAS BOND
7. SERVICE ENERGIZED PRIOR TO APPROVAL