Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/12/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 03/12/2008 | ELECTRIC - FINAL | Approved | 1) CLEARANCES APPROVED BY J. JAWORSKY | |
| 12/20/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. MAINTAIN WORKING CLEARANCES 110.26 2. PLEASE VERIFY PERMIT FOR NEW A/C 3. WHERE IS WATER & GAS BONDING 4. BOND JUNCTION BOX ENCLOSURE 5. CABLES ENTERING BACK OF BOX TO BE SECURED TO BOX |