Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T07EL02089

Parcel: 117081120


Addresses:

821 S 8TH AV

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
01/29/2008 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
01/28/2008 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL BOND BUSHING AT END OF CONDUIT FOR GROUNDING ELECTRODE SYSTEM
2. GAS BOND NEEDS TO BE ON CUSTOMER SIDE OF GAS METER