Permit: T07EL02085

Parcel: 112074300


Addresses:

2520 N STEWART AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/06/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
12/04/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. EQUIPMENT GROUND #6 & SMALLER TO BE GREEN ENTIRE LENGTH - NEC 250.119
2. PANEL DIRECTORY'S STILL NOT IDENTIFIED - NEC 408.4
3. WATER BOND CLAMP LOOSE, BONDING CONDUCTOR ANCHORS NOT HOLDING/ROMEX STAPLES NOT LISTED FOR OUTDOOR USE/POORLY INSTALLED
4. STILL NEED TO COMPLETE #7 & #9 FROM PREVIOUS INSPECTION
5. AT SUB-PANEL, INSTALL MISSING COVER SCREWS, REMOVE CLAMPS AND GROUNDS TO EMT, BONDING CORRECTION WAS FOR WATER & GAS PIPES

DO NOT CALL BEFORE ALL CORRECTIONS COMPLETE
11/30/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. IDENTIFY PANEL DIRECTORIES - NEC 408.4
2. ANCHORS NOT HOLDING - NEC 110.73
3. USE PROPERLY SIZED EMT STRAPS - NEC 110.3B
4. EMT (BOTH) OVERFILLED - NEC TABLE C.1(A)
5. BOND ALL METAL PIPING TO SERVICE - NEC 250.104
6. A PERMIT IS NEEDED FOR NEW AC & CKT
7. PROVIDE PROPER WORKING CLEARANCE IN FRONT OF SUB-PANEL - NEC 110.26
8. INSTALL STRUT CLAMP FOR EMT ABOVE SUB-PANEL
NEC 110
9. SUB-PANEL COVER NOT WORKING PROPERLY