Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/06/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 12/04/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. EQUIPMENT GROUND #6 & SMALLER TO BE GREEN ENTIRE LENGTH - NEC 250.119 2. PANEL DIRECTORY'S STILL NOT IDENTIFIED - NEC 408.4 3. WATER BOND CLAMP LOOSE, BONDING CONDUCTOR ANCHORS NOT HOLDING/ROMEX STAPLES NOT LISTED FOR OUTDOOR USE/POORLY INSTALLED 4. STILL NEED TO COMPLETE #7 & #9 FROM PREVIOUS INSPECTION 5. AT SUB-PANEL, INSTALL MISSING COVER SCREWS, REMOVE CLAMPS AND GROUNDS TO EMT, BONDING CORRECTION WAS FOR WATER & GAS PIPES DO NOT CALL BEFORE ALL CORRECTIONS COMPLETE |
|
| 11/30/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. IDENTIFY PANEL DIRECTORIES - NEC 408.4 2. ANCHORS NOT HOLDING - NEC 110.73 3. USE PROPERLY SIZED EMT STRAPS - NEC 110.3B 4. EMT (BOTH) OVERFILLED - NEC TABLE C.1(A) 5. BOND ALL METAL PIPING TO SERVICE - NEC 250.104 6. A PERMIT IS NEEDED FOR NEW AC & CKT 7. PROVIDE PROPER WORKING CLEARANCE IN FRONT OF SUB-PANEL - NEC 110.26 8. INSTALL STRUT CLAMP FOR EMT ABOVE SUB-PANEL NEC 110 9. SUB-PANEL COVER NOT WORKING PROPERLY |