Permit: T07EL02084

Parcel: 128140080


Addresses:

625 S ROSEMONT AV

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/06/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. COMPLETE ITEM #1 & #8 FROM PREVIOUS INSPECTION
2. NOT ENOUGH NEUTRAL CONDUCTORS FOR DRYER, COOLER, AND STORAGE CIRCUITS ONLY ONE NEUTRAL FOR 4 PHASE CONDUCTORS
3. STILL UNABLE TO VERIFY GAS BONDING
12/04/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. GROUNDING CONDUCTOR TO BE MARKED ALONG ENTIRE LENGTH #6 & SMALLER - NEC 250.119
2. NEUTRAL CONDUCTOR TO BE MARKED ALONG ENTIRE LENGTHI #6 & SMALLER - NEC 200.6
3. DIMMER SWITCHES TO CONTROL PERMANENTLY INSTALLED INCANDESCENT LUMINARIES. CANNOT BE USED ON RECEPTACLE. NEC 404.14(E)
4. SWITCHES LOCATED OUTSIDE OF BUILDINGS TO BE ENCLOSED IN WEATHERPROOF ENCLOSURE - NEC 404.4
5. WATER BOND NOT SIZED PROPERLY - NEC 250.104 & 250.66
6. BOND GAS PIPING - NEC 250.104
7. SERVICE ENERGIZED PRIOR TO APPROVAL
8. CONNECT GROUNDING CONDUCTOR TO METAL BOXES -
NEC 250.148
9. CANNOT READ PANEL DIRECTORY - NEC 408.4
11/30/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*