Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/06/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. COMPLETE ITEM #1 & #8 FROM PREVIOUS INSPECTION 2. NOT ENOUGH NEUTRAL CONDUCTORS FOR DRYER, COOLER, AND STORAGE CIRCUITS ONLY ONE NEUTRAL FOR 4 PHASE CONDUCTORS 3. STILL UNABLE TO VERIFY GAS BONDING |
|
| 12/04/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. GROUNDING CONDUCTOR TO BE MARKED ALONG ENTIRE LENGTH #6 & SMALLER - NEC 250.119 2. NEUTRAL CONDUCTOR TO BE MARKED ALONG ENTIRE LENGTHI #6 & SMALLER - NEC 200.6 3. DIMMER SWITCHES TO CONTROL PERMANENTLY INSTALLED INCANDESCENT LUMINARIES. CANNOT BE USED ON RECEPTACLE. NEC 404.14(E) 4. SWITCHES LOCATED OUTSIDE OF BUILDINGS TO BE ENCLOSED IN WEATHERPROOF ENCLOSURE - NEC 404.4 5. WATER BOND NOT SIZED PROPERLY - NEC 250.104 & 250.66 6. BOND GAS PIPING - NEC 250.104 7. SERVICE ENERGIZED PRIOR TO APPROVAL 8. CONNECT GROUNDING CONDUCTOR TO METAL BOXES - NEC 250.148 9. CANNOT READ PANEL DIRECTORY - NEC 408.4 |
|
| 11/30/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |