Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/17/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 12/06/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 12/04/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. 60 AMP BREAKER OVERSIZED FOR #8 CONDUCTOR SEE 310 NEC - ALSO #2 CONDUCTORS FOR SUB-PANEL SHOULD BE ON 100 AMP MAX CB 2. USE 1/4" MIN. BOLT TO SUPPORT RISER 3. CONDUCTORS ON 50 AMP TO GUEST HOUSE TAPPED, VERIFY MARKING ON INSULATION FOR LISTING |
|
| 11/29/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |