Permit: T07EL02060


Addresses:

7032 S APRON DR

Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Date Description Inspector Results Comments
02/08/2008 ELECTRIC - UNDERGROUND Approved IVRS - Inspection :*
OK GROUND RODS & GROUNDING ELECTRODE CONDUCTOR
TO DISC. SW AT SERVICE
02/07/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1. METAL RACEWAY FOR GROUNDING ELECTRODE CONDUCTOR MUST BE BONDED TO ELECTRODE CONDUCTOR AS REQUIRED PER 250.64E
2. SUPPORT RACEWAY FOR GROUNDING ELECTRODE CONDUCTOR
01/30/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
- OK CONDUITS, SECONDARY FROM TEP X-FORMER TO NEW SERVICE LOCATION, ALSO 1 1/2" FEEDER TO SKID
- NO GROUNDING YET - BE SURE TO GROUND PER 250 NEC