Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE RELOCATION
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/10/2008 | ELECTRIC - SERVICE RELOCATION | Approved | IVRS - Inspection :* | |
| 12/21/2007 | ELECTRIC - SERVICE RELOCATION | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) COMPLETE ITEM #2 FROM INSPECTION ON 12/19/07 2) CANNOT USE WHITE WIRE FOR GROUNDING CONDUCTOR. GROUNDING CONDUCTOR #6 AND SMALLER TO BE INDENTIFIED ALONG ENTIRE LENGTH. NEC 250.119 3) RECALL WHEN READY |
|
| 12/19/2007 | ELECTRIC - SERVICE RELOCATION | Partial Approval | IVRS - Inspection :* 1) NEED DETAILED PANEL DIRECTORY NEC. 408.4 2) CONNECT EQUIPMENT GROUNDING CONDUCTOR TO 12" X 12" JUNCTION BOX NEC. 250.148 3) BONDING JUMPER TO WATER PIPING NOT SIZED PROPRERLY NEC 250.104 4) SEAL OPENING THRU BACK OF 12" X 12" JUNCTION BOX WITH NON-COMBUSTIBLE MATERIAL/SEALANT 5) MAST BRACING TO BE INSTALLED PROPERLY 6) GROUNDING CONDUCTOR FOR DRYER CIRCUIT NOT SIZED PROPERLY NEC 250.122 7) CLEAN OUT DEBRIS FROM BOTTOM OF PANEL |