Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/30/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/29/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CANCELED BY CONTRACTOR |
|
| 04/22/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEED TO PULL PERMIT FOR NEW AC UNIT 2. WHEN USING CHASE NIPPLE USE LOCK NUT FOR GOOD CONTACT METAL TO METAL FOR CONNECTION OF LB 3. STRAP ROMEX WITHIN 12" OF CONNECTION TO BOX & PANEL 4. 4/3 ROMEX AMPACITY IS 70 AMP NOT 100AMP NEC 334.80 AND NEC 310.16 5. SEAL OPEN KNOCKOUT TOP OF SUB-PANEL 6. VERIFY 6" X 6" JUNCTION BOX IS GROUNDED |