Permit: T07EL02055

Parcel: 135041750

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/30/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/29/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CANCELED BY CONTRACTOR
04/22/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEED TO PULL PERMIT FOR NEW AC UNIT
2. WHEN USING CHASE NIPPLE USE LOCK NUT FOR GOOD CONTACT METAL TO METAL FOR CONNECTION OF LB
3. STRAP ROMEX WITHIN 12" OF CONNECTION TO BOX & PANEL
4. 4/3 ROMEX AMPACITY IS 70 AMP NOT 100AMP
NEC 334.80 AND NEC 310.16
5. SEAL OPEN KNOCKOUT TOP OF SUB-PANEL
6. VERIFY 6" X 6" JUNCTION BOX IS GROUNDED