Permit: T07EL02050

Parcel: 110030890

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07EL02050

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/27/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
12/24/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
12/17/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. FINISH PREVIOUS ITEMS

* REFEE MAY BE ACCESSED IF ITEMS NOT CORRECTED
12/11/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. USE CORRECT COVERS FOR CONDUCTORS - CANNOT TAPE GREEN
2. NEED BUSHING ON CONDUIT & NIPPLES
3. CORRECTLY INSTALL GROUNDING ELECTRODE CONDUCTOR
4. MARKING OF UNIT # TO BE PERMANENT
5. FINISH #4 & #5 OF PREVIOUS ITEMS - CUSTOMER IS REWIRING TRAILER NEED SEPARATE PERMIT.
11/27/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) MARK UNIT NUMBER AT METER DISCONNECT
2) DISCONNECT AT UNIT MISSING DEAD FRONT
3) SEAL OPEN KNOCKOUTS IN DISCONNECT
4) PLEASE VERIFY PERMIT ALL NEW ELECTRIC WORK DONE TO INTERIOR OF UNIT
5) UNIT UNSAFE TO TURN ON HAVE NEW WIRES JUST HANGING OUT OF WALLS AND ALL THIS WORK NEEDS TO BE INSPECTED AND APPROVED BEFORE POWER WILL BE RESTORED