Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07EL02050
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/27/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
12/24/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
12/17/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. FINISH PREVIOUS ITEMS * REFEE MAY BE ACCESSED IF ITEMS NOT CORRECTED |
|
12/11/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. USE CORRECT COVERS FOR CONDUCTORS - CANNOT TAPE GREEN 2. NEED BUSHING ON CONDUIT & NIPPLES 3. CORRECTLY INSTALL GROUNDING ELECTRODE CONDUCTOR 4. MARKING OF UNIT # TO BE PERMANENT 5. FINISH #4 & #5 OF PREVIOUS ITEMS - CUSTOMER IS REWIRING TRAILER NEED SEPARATE PERMIT. |
|
11/27/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MARK UNIT NUMBER AT METER DISCONNECT 2) DISCONNECT AT UNIT MISSING DEAD FRONT 3) SEAL OPEN KNOCKOUTS IN DISCONNECT 4) PLEASE VERIFY PERMIT ALL NEW ELECTRIC WORK DONE TO INTERIOR OF UNIT 5) UNIT UNSAFE TO TURN ON HAVE NEW WIRES JUST HANGING OUT OF WALLS AND ALL THIS WORK NEEDS TO BE INSPECTED AND APPROVED BEFORE POWER WILL BE RESTORED |