Permit: T07EL02040

Parcel: 134050170


Addresses:

759 S SANTA ANA DR

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/14/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
12/05/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) INSTALL BREAKERS LISTED FOR USE IN SIEMENS PANEL
2) INSTALL PROPER SIZE STRAPS ON MAST
11/23/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. REMOVE STRAP FROM IN FRONT OF SERVICE PANEL
2. PROVIDE PROTECTIVE BUSHING WHERE CABLES
ENTER 3/4" EMT
3. CAN ONLY LOCATE ONE GROUND ROD - PLEASE UNCOVER AND MARK
4. STRAP MAST TO BUILDING USING 1/4" HARDWARE MIN.
5. CONNECT SERVICE CONDUCTORS TO OVERHEAD POSITION IN METER SECTION
6. MIN. SIZE SERVICE CONDUCTORS FOR 200 AMP IS 2/0 COPPER OR 4/0 AL
7. INSTALL BREAKERS LISTED FOR USE IN SIEMENS PANEL
8. SEAL OPEN KNOCKOUTS
9. SEAL OPENING WHERE WIRES ENTER BACK OF PANEL WITH NON-COMBUSTIBLE MATERIAL
10. CONNECT ALL GROUNDS TO GROUND BAR SEE MAX # PER TERMINATION ON PANEL COVER
11. CHECK ALL STRANDS UNDER TERMINALS
12. ARE THERE SPIKES IN LB? NEED 6" MIN. OF FREE CONDUCTOR LENGTH. CHECK WIRE FILL ON LB
13. STRAP SEAL TIGHT TO AC DISCONNECT