Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/18/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED TO USE SEALING TYPE LOCK NUTS WHERE NIPPLES ENTER SERVICE 2) SEAL HOLES IN WALL AROUND NIPPLES 3) PANEL DIRECTORY TO BE COMPLETE AND CORRECT |
|
| 12/10/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The service is not per code.| 210* 1. NEED LISTED MAST BRACE 2. FINISH GROUNDING & BONDING 3. SECURE MAST ABOVE SERVICE 4. ROMEX SHEATHING TO ENTER ENCLOSURE MINIMUM 1/4" 5. ENTRIES INTO ENCLOSURE TO BE MADE RAINTIGHT/WEATHERPROOF PARTIAL INSPECTION ONLY |