Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/07/2007 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
| 12/03/2007 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 11/19/2007 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) EQUIPMENT GROUNDING CONDUCTOR FOR DRYER CIRCUIT NOT SIZED PROPERLY NEC 250 2) NEUTRAL CONDUCTORS TO BE IDENTIFIED ALONG ENTIRE LENGTH #6 AND SMALLER NEC 200 3) SEAL OPEN KNOCK OUTS NEC 110 4) DRYER CIRCUIT TO ENTER IN TOP RIGHT HAND SIDE OF PANEL ENCLOSURE PER MANUFACTURERS INSTRUCTIONS NEC 110 5) CAN ONLY LOCATE ONE GROUND RED PLEASE UNCOVER AND MARK LOCATION 6) GROUNDING ELECTRODE ? FOR #2 TO CONNECT TO GROUNDING ELECTRODE CONDUCTOR. BOND GAS AND WATER TO BOTH SERVICES. NEC 250 HAVE 2 GAS SERVICES 7) SPLICES IN METER SECTION NOT ACCESSIBLE 8) METER SECTIONS SEALED PRIOR TO INSPECTION AND APPROVED 9) GROUNDING CONDUCTORS TO BE GREEN ON BARE NEC 250 |