Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/20/2007 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
| 11/19/2007 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSTALL MISSING DEVICE PLATES 2) INSTALL SMOKE DETECTOR IN BEDROOM PER MANUFACTURER INSTRUCTIONS 3) SMOKE DETECTORS OUTSIDE BEDROOM TO BE OPERATIONAL 4) BATHROOM LIGHT FIXTURE TO BE REPAIRED/REPLACED 5) CANNOT USE ROMEX FOR CORD ON FURNACE 6) SEAL OPEN 1/2" EMT COMING OUT THE TOP OF SERVICE PANEL 7) INSTALL CONNECTOR ON SJ CORD TO COOLER 8) SEWER SEAL TIGHT ON ROOF 9) STRAP EMT ON BACK PORCH 10) INSTALL K.O. SEALS BOXES BACK PORCH 11) DO NOT HAVE PROPER WORKING CLEARANCES ON SUB PANEL IN WATER HEATER CLOSET |