Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/29/2008 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
| 01/15/2008 | ELECTRIC - RECONNECT | Partial Approval | IVRS - Inspection :* | |
| 12/14/2007 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SERVICE NOT CONNECTED AT GROUND TO WATER PIPE 2) MULTIPLE LUGGING AT SERVICE MAIN 3) OUTDOORS AT EVE'S WIRING UNPROTECTED, BOXES NOT WEATHERPROOF 4) OUTLET BELOW SERVICE TO BE WEATHERPROOF 5) NEW LIGHTING ON BACK ROOM WIRING NOT INSPECTED 6) NEW PLUMBING AT WASHER 7) WIRING TO FLOURESCENT LTS IN REMODELED GARAGE, WIRING IMPROPER 8) BACK BEDROOMS HAVE BEEN UNCLOSED AND MADE IN HABITABLE ROOMS 9) WASH ROOM RECEPTACLE-EXPOSED ROMEX AT RECEPTACLE 10) ALL BEDROOMS MUST HAVE SMOKE DETECTORS 11) NEW GAS LINE ADDED IN WASH ROOM 12) CANNOT LOCATE CIRCUIT BREAKER PANEL 13) BACK AND EAST SIDE BEDROOM APPEAR TO HAVE BEEN ADDED WITH PERMITS, GARAGE APPEARS TO HAVE BEEN ADDED WITHOUT PERMITS. PLEASE CHECK TO SEE IF PERMITS WERE EVER OBTAINED FOR ADDITIONS IF NOT YOU HAVE TO OBTAIN THEM AT 201 N. STONE |
|
| 11/21/2007 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* TOO MANY ELECTRICAL, PLUMBING AND STRUCTURAL PROBLEMS. MAIN PANEL AND DISCONNECTS LOCKED WITH METER REMOVED. REFERRED TO DNR. |
|
| 11/20/2007 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : There is no access to the site.| 920* UNIT LOCKED - MUST BE OPEN FOR INSPECTION NO MESSAGE RECALL INSP. |