Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/30/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 11/27/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
| 11/14/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. LABEL CIRCUIT DIRECTORY PER 408.4 - NO ABBREVIATION AND DISTINGUISHABLE FROM ONE ANOTHER 2. FILL UNUSED OPENING IN PANEL ALSO, UNUSED PORTION OF OPENING IN BACK OF PANEL WITH A NON-COMBUSTIBLE PRODUCT 3. PLEASE VERIFY PERMIT FOR NEW AC UNIT & MAINTAIN WORKING CLEARANCES 110.26 4. STRAP GROUNDING ELECTRODE CONDUCTOR TO STRUCTURE 5. DRIVE 1ST ROD FLUSH WITH SURFACE |