Permit: T07EL02018

Parcel: 133050070


Addresses:

1231 N BEDFORD PL

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
11/30/2007 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
11/14/2007 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL BREAKERS LISTED FOR USE IN SQUARE D PANEL
2. INSTALL PROPER FITTING FOR CONNECTION OF LB TO PANEL
3. STRAP EMT WITHIN 3' OF CONNECTION POINTS TO LB'S AND PANEL
4. PLEASE VERIFY PERMIT FOR NEW AC UNIT. PROVIDE COPY OF PERMIT
5. CANNOT VERIFY BONDING OF WATER & GAS PIPING. NEED TO SEE BONDING JUMPER ENTIRE LENGTH. WATER BOND TO BE SIZED PER 250.104 & 250.66 BASED ON SIZE OF SERVICE ENTRANCE CONDUCTORS
6. WAS SUB-PANEL ON 70 AMP BREAKER/FUSES ON OLD SERVICE OR SHOULD IT BE ON 60 AMP BREAKER.