Permit: T07EL01985

Parcel: 120052080


Addresses:

4561 S 14TH AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/07/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/23/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
CALL FOR FINAL INSP. AFTER TIE IN
11/09/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. RISER NEEDS TO BE RIGID CONDUIT
2. 2 GROUND RODS REQUIRED 6' APART
3. BOND WATER & GAS PIPING
4. I.D NEUTRAL RISER CONDUCTOR
5. STRAP RISER CONDUIT, USE 1/4" BOLTS
6. INSTALL BUSHING IN BACK OF PANEL WHERE CABLES GO THROUGH