Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/07/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 11/23/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* CALL FOR FINAL INSP. AFTER TIE IN |
|
| 11/09/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. RISER NEEDS TO BE RIGID CONDUIT 2. 2 GROUND RODS REQUIRED 6' APART 3. BOND WATER & GAS PIPING 4. I.D NEUTRAL RISER CONDUCTOR 5. STRAP RISER CONDUIT, USE 1/4" BOLTS 6. INSTALL BUSHING IN BACK OF PANEL WHERE CABLES GO THROUGH |