Inspection History: ELECTRIC - CABLE DROP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/27/2007 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :* | |
| 11/20/2007 | ELECTRIC - CABLE DROP | Partial Approval | IVRS - Inspection :* - INSTALL HOLD DOWN DEVICE FOR MAIN BKR. IN MODULE PANEL - FILL IN ALL UNUSED OPENINGS IN DEADFRONT - STRAP #4 BARE TO PEDESTAL |
|
| 11/16/2007 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. VERIFY 2 GROUND RODS 6' MIN. APART 2. INSTALL PERMANENT ADDRESS LABEL ON SERVICE PEDESTAL 3. CONNECTION NOT MADE TO OFFICE TRAILER |