Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
Permit Number - T07EL01982
Inspection Description - ELECTRIC - SERVICE UPGRADE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/03/2008 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
12/21/2007 | ELECTRIC - SERVICE UPGRADE | Cancelled | IVRS - RI canceled | |
12/17/2007 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL GROUNDING ELECTRODE SYSTEM - NEC 250 2. BONDING JUMPER ON BONDING BUSHING NOT SIZED PROPERLY - NEC 250 3. INSTALL BREAKERS LISTED FOR USE IN SIEMENS PANEL 4. SEAL OPENING WHERE WIRES ENTER PANEL WITH NON-COMBUSTIBLE MATERIAL 5. BOND GAS & WATER PIPING - NEC 250 6. SERVICE CONDUCTORS NOT SIZED PROPERLY - NEC 310 7. SERVICE ENERGIZED PRIOR TO APPROVALS. CANNOT SEE INTO METER SECTION 8. CANNOT USE SHEETMETAL SCREWS FOR CONNECTION OF GROUNDS - NEC 250 |