Permit: T07EL01982

Parcel: 136173960


Addresses:

8357 E CAMARILLO DR


Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Permit Number - T07EL01982

Inspection Description - ELECTRIC - SERVICE UPGRADE

Inspection Status - Approved

Date Description Inspector Results Comments
11/03/2008 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
12/21/2007 ELECTRIC - SERVICE UPGRADE Cancelled IVRS - RI canceled
12/17/2007 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL GROUNDING ELECTRODE SYSTEM - NEC 250
2. BONDING JUMPER ON BONDING BUSHING NOT SIZED PROPERLY - NEC 250
3. INSTALL BREAKERS LISTED FOR USE IN SIEMENS PANEL
4. SEAL OPENING WHERE WIRES ENTER PANEL WITH NON-COMBUSTIBLE MATERIAL
5. BOND GAS & WATER PIPING - NEC 250
6. SERVICE CONDUCTORS NOT SIZED PROPERLY - NEC 310
7. SERVICE ENERGIZED PRIOR TO APPROVALS. CANNOT SEE INTO METER SECTION
8. CANNOT USE SHEETMETAL SCREWS FOR CONNECTION OF GROUNDS - NEC 250