Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/21/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 11/23/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* BRACING TO BE THREADED NOT CONNECTORS WITH EMT ALSO INTO TRUSS NOT JUST ROOF |
|
| 11/08/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. RECEPTACLE COVER TO BE AS PER 406.8 2. TIGHTEN LOOSE FITTINGS 3. FILL UNUSED PORTION OF OPENING IN BACK OF PANEL WITH A NON-COMBUSTIBLE PRODUCT 4. ONLY ONE NEUTRAL TERMINATION TO A LUG 5. PROVIDE A LISTED MAST BRACE DUE TO DISTANCE TO POLE 6. PLEASE VERIFY GAS BOND 7. PROVIDE PAPERWORK FROM MANUFACTURE FOR CONNECTIONS OF SERVICE FEEDERS * SERVICE ENERGIZED WITHOUT CLEARANCE |