Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/19/2007 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
| 11/13/2007 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSTALL BREAKERS LISTED FOR USE IN MURRAY PANEL NEC 110.3 2) NEED PANEL DIRECTORY PER NEC 408.4 3) CLEANOUT DIRT AND OIL FROM PANEL NEC 110.12 4) NEED MINIMUM 10' CLEARANCE ABOVE GRADE TO OPEN CONDUCTORS NEC 225.18 5) INSTALL LISTED RESTROOM LIGHTING NEC 110.3, 525.20 6) USE PROPER SIZE STRAPS FOR SUPPORTS ON EMT |