Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/28/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 11/26/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. PROTECT CONDUCTORS AT FITTING 300.4 2. CORRECTLY IDENTIFY UNGROUNDED CONDUCTOR - TO BE FULL LENGTH IN RACEWAY 3. MAINTAIN WORKING SPACE AS DISCUSSED IN FRONT OF PANEL 4. CORRECTLY IDENTIFY GROUNDED CONDUCTOR 200.6 OLD SYSTEM IS UNGROUNDED SYSTEM |
|
| 11/21/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* FINISH LOAD SIDE AND RECALL BY 11/26/07 |